Basic Info
Product Description
1151 type transmitter has many kinds of models which can
measure micro-differential pressure to large differential pressure, low
pressure to high pressure, level, vacuum and gravity. If it is matched
with throttling device, it can measure flow without square root
extractors. Flange level transmitter includes flat flange and insert
flange. The installation includes 3# and 4#, 150#(working pressure is
1.89Mpa)and 300#(working pressure is 4.95Mpa). In addition to 316
stainless steel-wetted materials, there is Hastelloy, Monel metal and
tantalum which can be used in corrosive media.
1151 type transmitter is compact with explosion-proof and all-weather structure. The installation and operation are simple. Terminals and amplification circuit can be placed in the upper chamber in the closed electrical and separated from each other. Therefore, when it is field wiring, the AMP was still working under the closed state. Amplification circuit has reverse polarity protection to prevent damaging to the transmitter.
1151DR | Capacitive pressure transmitter | |||||
code | range | |||||
2 | 0-0.2 to 1.49 kPa | |||||
code | output | |||||
F | 4~20mA DC | |||||
code | Structure and material | |||||
Pressure chamber and the joint | Relief valves | Isolated diaphragm | ||||
12 | Cadmium plated carbon steel | 316SST | 316L SST | |||
22 | 316SST | 316SST | 316L SST | |||
code | Selected items | |||||
M1 | Linear root indicator,0~100% | |||||
M2 | Square root indicator,0~10 | |||||
B1 | Bend rack tube mounted(ø51 mm tube) | |||||
B2 | Bend rack plate mounted | |||||
B3 | Flat rack tube mounted(ø51 mm tube) | |||||
D1 | relief valves in the side of the upper volume chamber | |||||
D2 | relief valves in the side of the upper volume chamber | |||||
Ed | Explosion-proof type anti-explosion dIICT6 | |||||
Ei | Intrinsically Safe type anti-explosion dIICT6(without safety barrier) | |||||
1151DR | 2 | F | 22 | M\B\D\E | Complete model of transmitter |